Description
These cables are indicated for industrial connections, control of solenoid valves, machine start-up, robots and internal distribution installations. It can be used in underground networks and permanent installations. The special construction of these cables affords high flexibility, making them very appropriate in complex and extremely difficult installations.
Applications
Outdoor lighting installations.
Indoor or receiver installations
1. Conductor
Flexible electrolytic copper conductor (Class V) according to BS EN 60228:2005 (previously BS6360) and UNE 60228.
2. Insulation
PVC insulation, type A, according to UNE 21123 and IEC 60502-1.
3. Sheathing
PVC sheath, type ST-1, according to UNE 21123 and IEC 60502-1.
Rated voltage
0,6/1kV
Test voltage
3.500V in A.C.
Maximum temperature
70ºC
Other characteristics
Colours according to UNE 21089 (marked with colours for less than five conductors) and HD 308S2:2001
Colours according to UNE-EN 50334 (marked by inscription for more than five conductors) and EN 50334:2001
Non-flame propagating according to UNE-EN 60332, EN 60332 and IEC 60332
PVC insulation and sheath with reduced hydrogen chloride (HCL) emission
National norm / european
EN 60332-1
International norm
IEC 60332-1
Section (mm2 )
Resistance at 20ºC (Ω/km)
External Diameter (mm)
Weight (kg/km)
6G1,5
13,30
12,29
235
6G2,5
7,98
13,57
315
7G1,5
13,30
12,20
245
7G2,5
7,98
13,46
330
8G1,5
13,30
13,19
285
8G2,5
7,98
14,61
385
10G1,5
13,30
15,30
355
10G2,5
7,98
16,98
475
12G1,5
13,30
15,80
390
12G2,5
7,98
17,54
530
14G1,5
13,30
16,60
435
16G1,5
13,30
17,53
495
16G2,5
7,98
19,50
670
19G1,5
13,30
18,49
560
19G2,5
7,98
20,70
765
24G1,5
13,30
21,58
710
24G2,5
7,98
24,10
975
27G1,5
13,30
24,20
804
27G2,5
7,98
26,60
1.114
30G1,5
13,30
24,40
874
30G2,5
7,98
27,60
1.217
33G1,5
13,30
25,40
947
33G2,5
7,98
27,80
1.238
37G1,5
13,30
26,30
1.040
37G2,5
7,98
30,00
1.468
Cables available with up to 61 conductors