Description
These cables are indicated for executing wiring installations for meter centralisation, boards, panels and especially when low fumes and corrosive gas emission, as well as improved temperature behaviour are required.
Applications
Meter centralisation
Public premises
1. Conductor
Electrolytic copper conductor, Class II, according to BS EN 60228:2005 (previously BS6360) and EN 60228.
2. Insulation
Thermostable material insulation with polyolefin base and low smoke and corrosive gas emission, type EI-5, according to UNE 21027-9 and HD 222007.
Rated voltage
450/750V
Test voltage
2.500V in A.C.
Maximum temperature
90ºC
Other characteristics
Colours according to UNE 21027 and HD 22.1S4
Non-flame propagating according to UNE-EN 60332, EN 60332, IEC 60332
Non-fire propagating according to UNE-EN 50266, EN 50266
Low halogen content according to UNE 21027-9 and HD 22.9S3:2007
Low corrosive gas emission according to UNE 21027-9 and HD 22.9S3:2007
Low opaque smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034
National norm / european
EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034
International norm
IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034
Section (mm2 )
Resistance a 20ºC (Ω/km)
External Diameter (mm)
Weight (kg/km)
1,5
12,10
3,00
23
2,5
7,41
3,70
35
4
4,61
4,20
51
6
3,08
4,50
64
10
1,83
6,00
111
16
1,15
6,70
158